ServiceManual
AIR CONDITIONER
KSIMUNITS0912.000BTU/H
3D DC Inverter
Split Wall-Mounted Type





ModelRefrigeranttypePowersupply
KSIM009H210  R410A230/208V,60Hz,1Ph
KSIM012H210  R410A230/208V,60Hz,1Ph

KSIM SERIES
Seitenansicht 0
1 2 3 4 5 6 ... 41 42

Inhaltsverzeichnis

Seite 1 - ServiceManual

  ServiceManual AIR CONDITIONER KSIMUNITS09–12.000BTU/H3D DC Inverter Split Wall-Mounted Type

Seite 2 - CONTENTS

73.2 Outdoor Unit

Seite 3

8 4. Refrigerant cycle diagram

Seite 4 - 1. Precaution

95. Wiring diagram 5.1 Indoor Unit

Seite 5 - ¾ Operational

10 5.2 Outdoor Unit

Seite 6

116. Installation details 6.1 Tightening Connection Align the center of the pipes. Sufficiently tighten the flare nut with fingers, and then tig

Seite 7 - 2. Function

12Capacity is base on standard length and maximum allowance length is base of reliability. Oil trap should be installed per 5-7 meters. 6.4 Air

Seite 8

13retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of ga

Seite 9 - 3. Dimension

146.5 Pumping down (Re-installation) Procedure 1. Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve st

Seite 10 - 3.2 Outdoor Unit

156.6 Re-air purging (Re-installation) Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the closed position. 2. Connect the c

Seite 11 - 4. Refrigerant cycle diagram

166.7 Balance refrigerant of the 2-way, 3-way valves Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the open position. 2.

Seite 12 - 5. Wiring diagram

CONTENTS 1. Precaution ...

Seite 13 - 5.2 Outdoor Unit

176.8 Evacuation Procedure: 1. Connect the vacuum pump to the charge set’s centre hose. 2. Evacuation for approximately one hour. Confirm that the

Seite 14 - 6. Installation details

186.9 Gas charging Procedure: 1. Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacuum

Seite 15

197. Operation characteristics 7.1 KSIM009-H219 Heating Capacity (KW) Piping Length Characteristics (Heating) Piping Length (m) 2.7 2.6 2.4 2.5 2.

Seite 16

207.2 KSIM012-H220 Remark: Indoor room temperature: 20 Indoor fan speed: High Pipe length: 5m Piping Length (m) 10 11 12 13 14 5

Seite 17

218. Electronic function 8.1 Abbreviation T1: Indoor ambient temperature T2: Pipe temperature of indoor heat exchanger T3: Pipe temperature

Seite 18

228.3 Protection 8.3.1 Three Minutes Delay at restart for compressor. 8.3.2 Temperature protection of compressor top. 8.3.3 If the tempera

Seite 19

238.5 Cooling Mode 8.5.1 The operation frequency of compressor after starting submits to following rule. When the machine is running and ΔT(=ro

Seite 20 - 6.8 Evacuation

248.5.6 Indoor fan operation rule. 1) In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and au

Seite 21 - 6.9 Gas charging

258.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential. Auto fan action in heating m

Seite 22 - 7. Operation characteristics

268.7.6 Defrosting mode. 1) Condition of defrosting. Condition 1: If T4>0℃, When the units are running, if the foll

Seite 23 - 7.2 KSIM012-H220

8.18 Follow me function...

Seite 24 - 8. Electronic function

27rating value. Any condition of above is not satisfied, the machine can not be turned into rating capacity test mode. 2) The machine will quit fro

Seite 25 - 8.4 Fan-Only Mode

288.11 Two speeds outdoor fan function 8.11.1 Outdoor fan action in heating mode(including heating in auto mode). 8.11.2 Outdoor fan a

Seite 26 - 8.5 Cooling Mode

298.15 Automatic panel function 1) The automatic panel is forced to turn to the closing direction at an angle of 50°when the unit is getting throu

Seite 27 - 8.7 Heating mode

30At heating mode, if TA>TS, compressor is off; If TA≤TS, compressor is on. 4) The PCB will take action to the mode change information from remote

Seite 28

319. Troubleshooting Safety Because of there are capacitors in PCB and relative circuit in outdoor unit, even shut down the power sup

Seite 29

329.1 Indoor Unit Error Display Display LED STATUS E0 EEPROM parameter error E1 Indoor / outdoor units communication protection E2 Zero-crossing

Seite 30 - 8.10 Action of 4-way valve

339.2 Diagnosis and Solution 9.2.1 E0(EEPROM parameter error) error diagnosis and solution 9.2.2 E1(indoor / outdoor units communication pr

Seite 31 - 8.14 Auto-Restart function

349.2.4 E3(indoor fan speed out of control) diagnosis and solution 9.2.5 E5(Open or short circuit of outdoor temperature sensor) diagnosis a

Seite 32 - 8.18 Follow me function

359.2.8 P1(over voltage or too low voltage protection) diagnosis and solution. 9.2.9 P2(temperature protection of compressor top) diagnosis

Seite 33

369.3 Key parts checking. 9.3.1. Compressor checking (Model: DA108X1C-20FZ3). Measure the resistance value of each winding by using the mu

Seite 34 - 9. Troubleshooting

11. Precaution 1.1 Safety Precaution  To prevent injury to the user or other people and property damage, the following instructions must be follo

Seite 35

379.3.3 Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, O

Seite 36 - 9.2 Diagnosis and Solution

38 7909 N.W. 54th Street, Miami, FL 33166 USA Phone: +1 (305) 593-8358 Fax: + 1 (305) 593 8212 e-mail: s

Seite 38

2arrives. There is risk of property damage, failure of product, or electric shock.  Do not open the inlet grill of the product during operation. (

Seite 39 - 9.3 Key parts checking

3your skin or clothes, wash it well with clean Do not use the remote of the batteries have leaked. The chemical in batteries could cause burns or ot

Seite 40

42. Function When the power supply is interrupted and then restore, the air conditioners automatically restore the previous function setting. BLDC f

Seite 41

5 It protects the valves and prevents water from dripping.The unit has 3 mins delay between continuously ON/OFF operations.Outdoor unit Power relay

Seite 42

63. Dimension 3.1 Indoor Unit 285845165