Seite 1 - KSIN INVERTER SERIES

KSIN INVERTER SERIES Service Manual 2013

Seite 2 - CONTENTS

8 3. Dimension 3.1 Indoor Units DWH KSIN009-C115-IKSIN009-H115-IKSIN009-C215-IKSIN009-H215-IKSIN012-C115-IKSIN012-H115-IKSIN012-C215-IKSIN012-H215-I

Seite 3 - 1. Precaution

9 LRH Model R(mm) L(mm) H(mm) Dimension of installation hole(mm) 92 170 45 ¢65 95 170 45 80 100 45 Model R(mm) L(mm) H(mm) Dimension

Seite 4

10 3.2 Outdoor Units More than 30cmMore than 60cmMore than 70cmMore than 30cmMore than 60cm(Service space)Fence orobstacles Model W H D W1 A

Seite 5 - CAUTION

11 760 285 590 823 530 290 845 320 700 908 560 335 845 320 700 908 560 335 KSIN018-H215-OKSIN024-C215-OKSIN024-H215-O

Seite 6 - Operational

12 4. Refrigerant Cycle Diagram For cooling only models: INDOOR OUTDOORLIQUID SIDEGAS SIDEHEATEXCHANGE(EVAPORATOR)HEATEXCHANGE(CONDENSER)COMPRESSORC

Seite 7

13 For heat pump models: INDOOR OUTDOORLIQUID SIDEGAS SIDEHEATEXCHANGE(EVAPORATOR)HEATEXCHANGE(CONDENSER)COMPRESSOR2-WAY VALVE3-WAY VALVECHECK VALVE

Seite 8 - 2. Function

14 5. Wiring Diagram 5.1 Indoor Units KSIN009-C215-I, KSIN009-H215-I, KSIN012-C215-I, KSIN012-H215-I

Seite 9 - O: optional function

15 KSIN009-C115-I, KSIN009-H115-I, KSIN012-C115-I, KSIN012-H115-IKSIN018-C215-I, KSIN018-H215-I

Seite 10 - 3. Dimension

16 KSIN024-C215-O, KSIN024-H215-O

Seite 11

17 5.2 Outdoor Units KSIN009-C215-O, KSIN012-C215-O, KSIN012-H215-OKSIN009-C115-O, KSIN009-H115-O, KSIN012-C115-O, KSIN012-H115-O

Seite 12 - 3.2 Outdoor Units

CONTENTS 1. Precaution ... ... ...

Seite 13

18 KSIN018-C215-O, KSIN018-H215-O

Seite 14 - 4. Refrigerant Cycle Diagram

19 KSIN024-C215-O, KSIN024-H215-O

Seite 15 - INDOOR OUTDOOR

20 6. Installation details 6.1 Wrench torque sheet for installation Outside diameter Torque Additional tightening torque mm inch N.cm N.cm Ф6.

Seite 16 - 5. Wiring Diagram

21 6.3 Pipe length and the elevation The pipe length and refrigerant amount: Model Pipe size Standard length (m) Max. Elevation B (m) Max. Length

Seite 17

22 6.4 Installation for the first time Air and moisture in the refrigerant system have undesirable effects as below: ● Pressure in the system ris

Seite 18

23 the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -0.1Mpa after pu

Seite 19 - 5.2 Outdoor Units

24 Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ until the

Seite 20

25 6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose from the 3-way valve’s service port imme

Seite 21

26 6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side), disconnect the charge hose from th

Seite 22 - 6. Installation details

27 5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa. 6). Set the 3-way valve to the closed position

Seite 23

1 1. Precaution 1.1 Safety Precaution To prevent injury to the user or other people and property damage, the following instructions must be follow

Seite 24

28 Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ until the

Seite 25

29 2. Refrigerant charging Procedure: 1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve Connect the ch

Seite 26

30 Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage

Seite 27

31 7. Operation characteristics CAUTION: 1. If air conditioner is used outside of the above conditions, certain safety protection features may come

Seite 28

32 8. Electronic function 8.1 Abbreviation T1: Indoor ambient temperature T2: Coil temperature of indoor heat exchanger 8.2 Display function 8

Seite 29

33 8.3 Main Protection 8.3.1 Three Minutes Delay at restart for compressor 1 minute delay for the 1st time start-up and 3 minutes delay for others.

Seite 30

34 If T4>5℃ or the compressor starts running, the preheating function will stop. 8.3.8 Zero crossing detection error protection If AC detects time

Seite 31

35 8.4.2 Cooling Mode 8.4.2.1 Compressor running rules The maximum operation frequency of compressor after starting submits to following rule. 45434

Seite 32

36 F: Keep the current frequency. G: Decrease the frequency to the lower level until to F1. H: Run at F1 for 1h.(if T1-Ts<-2℃, the compressor wil

Seite 33 - 7. Operation characteristics

37 43HighLow1Medium1.5 8.4.2.4 Condenser temperature protection ---55℃<T3<60℃, the compressor frequency will decrease to the lower level until

Seite 34 - 8. Electronic function

2 condenser and evaporator. For installation, always contact the dealer or an Authorized service center. There is risk of fire, electric shock, ex

Seite 35 - 8.3 Main Protection

38 8.4.3 Heating Mode 8.4.3.1 Compressor running rules The maximum operation frequency of the compressor after starting submits to the following rul

Seite 36

39 +5.0+4.5+3.5+3.0+2.5+2.0+1.5+1.0HGFEDCBA+0.5 While the zones of A,B,C... are corresponding to different compressor running frequency. ΔT=0℃ as d

Seite 37

40 Hold: Keep the current frequency. Resume: No limitation for frequency. Note: When AC is in “hold” zone for 3 minutes, the compressor frequency

Seite 38 - Decrease

41 Indoor fan speed can be set as high, medium, low or auto fan and the anti-cold-wind function is preferential. Auto fan action in

Seite 39 - >=5℃

42 Defrosting action: For 9k,12k models: Compressoronoffonononoffoffoff4-way valveOutdoor fanIndoor fanIndoor fan breeze(10s)xx10sno longer than 10m

Seite 40

43 For 18k,22k models: Compressoronoffonononoffoffoff4-way valveOutdoor fanIndoor fanIndoor fan breeze(10s)xxno longer than 10mFrequency F830s10s10s

Seite 41

44 8.4.3.5 Evaporator coil temperature protection ----T2> TEH2℃, the compressor running frequency decreases to the lower level and runs for 20s.

Seite 42

45 2.01.51.0F3F2F1F12.50.50.0 8.4.5.3 Low indoor room temperature protection In drying mode, if room temperature is lower than 10℃, the compressor w

Seite 43

46 8.4.7.3 Timer off. The machine will turn off automatically when reaching the setting time. 8.4.7.4 Timer on/off. The machine will turn on automat

Seite 44

47 8.4.10 8℃ Heating(optional) In heating operation, the preset temperature of the air conditioner can be as lower as 8℃, which keeps the room te

Seite 45 - For 18k,22k models:

3 There is risk of explosion or fire. If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply

Seite 46

48 9. Troubleshooting 9.1 Indoor Unit Error Display Display Operation lamp flash times Timer lamp Failure E0 1 X EEPROM error E1

Seite 47

49 9.2 Diagnosis and Solution 9.2.1 EEPROM parameter error diagnosis and solution(E0/F4) If the EEPROM chip is welded on main PCB, replace the ma

Seite 48

50 9.2.2 Indoor / outdoor unit’s communication error diagnosis and solution(E1) YesYesMeasure Vs, is it moving alternately between positive value

Seite 49

51 9.2.3 Zero crossing detection error diagnosis and solution(E2) Check if the connections and power supply is normal?Correct the connections. Tur

Seite 50 - 9. Troubleshooting

52 Index 1: 1.Indoor AC Fan Motor Measure the resistance value of each winding by using the tester. Index2: 1: Indoor AC Fan Motor Power on and set

Seite 51 - 9.2 Diagnosis and Solution

53 9.2.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E4/E5/F1/F2/F3) Check the connections between temperature senso

Seite 52

54 9.2.5 IPM malfunction or IGBT over-strong current diagnosis and solution(P0) Check if the wiring between main PCB and compressor connected by err

Seite 53

55 9.2.6 Over voltage or too low voltage protection diagnosis and solution(P1) Check if the power supply is normal.Check if all the connections an

Seite 54

56 9.2.7 High temperature protection of compressor top diagnosis and solution(P2) Check if the air flow system of indoor and outdoor units are obs

Seite 55

57 9.2.8 Inverter compressor drive error diagnosis and solution(P4) Check if the wiring between main PCB and compressor connected by error and if th

Seite 56

4 It can avoid vibration of water leakage. Do not install the product where the noise or hot air from the outdoor unit could damage the neighborho

Seite 57

58 9.2.9 Refrigerant Leakage Detection diagnosis and solution(EC) Is there cool air blowing out from indoor air outlet?YesYesCheck if T2 sensor is w

Seite 58 - Measure the resistance

59 Safety Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity power in capa

Seite 59

60 Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3

Seite 60

61 Spec. Code 2T0032300786 2T0032300703 2T0032300704 2T0032300810 Indoor code 220032308400 220032307640 220032307650 220032308640 Indoor Out

Seite 61

62 Outdoor code 220037306370 Outdoor Compressor DA108X1C-23EZ Indoor fan motor RPG13B Outdoor fan motor YDK24-6KB KSIN009-C215-O

Seite 62 - T1,T2,T3,T4

63 2. Compressor checking Measure the resistance value of each winding by using the tester. Position Resistance Value DA108X1C-23EZ DA130

Seite 63 - MOR3-12HDN1-QC2

64 3.IPM continuity check Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digit

Seite 64 - KSIN009-C215-O

5 operated. There are sharp and moving parts that could cause personal injury. Do not drink the water drained from the product. It is not sanitary

Seite 65

6 2. Function Series Capacity Indoor units Outdoor units Inverter 9k 12k 18k 22k Model Names of Indoor/Outdoor UnitsKSIN009-C115-IKSIN009-H115-I

Seite 66

7 FilterIonizer(O)Silver Ico Filter(O)Vitamin C Filter(O)3M HAM Filter(O)Bio Filter(O)Killer Of FormaldehydeCompressor Crankcase Heater(O)Golden Fin